Our Comfort Modular range is designed for maximum flexibility. Individual sections house the fan and coil and can be linked in a
variety of ways to allow vertical or horizontal airflow. Chilled water and DX models are both available with either R22 or R407C
refrigerant and with cooling capacities from 9-43kW. A choice of controls and heating options, including Reverse Cycle Heat
Pump, are also available for maximum flexibility.
Chilled Water
Indoor Unit
Cooling Duty kW
Electric Heat Options kW
Power Supply
Fuse Size (A)
Indoor Dimension HxWxD mm
Indoor Weight Kg
CMCW3
9.2
7.5 or 15
400v 3ph 50Hz
6
1200x814x617
115
CMCW4
11.1
7.5 or 15
400v 3ph 50Hz
6
1200x814x617
115
CMCW5
12.6
7.5 or 15
400v 3ph 50Hz
6
1200x814x617
115
CMCW6
15.3
7.5 or 15
400v 3ph 50Hz
10
1200x1215x617
117
CMCW7.5
17.2
7.5 or 15
400v 3ph 50Hz
10
1200x1215x617
117
CMCW10
26.2
7.5 or 15
400v 3ph 50Hz
10
1200x1215x617
165
CMCW12
28.8
7.5 or 15 or 22.5
400v 3ph 50Hz
10
1200x1800x617
248
CMCW15
31.6
7.5 or 15 or 22.5
400v 3ph 50Hz
16
1200x1800x617
248
Cooling duty based on 27ºC Dry Bulb/ 19ºC Wet Bulb
and 7/12.0ºC water temperature. Nominal run amps are
recommended mains fuse relate to cooling only units.
DX
Cooling Only Indoor Unit Outdoor Unit
Cooling Duty kW
Elec Heat Options kW
Power Supply
Fuse Size (A)
Indoor Dimension HxWxD mm
Indoor Weight Kg
CMH3 & CUS3
9
7.5 or 15
400v 3ph 50Hz
6
1200x814x617
120
CMH4 & CUS4
12.6
7.5 or 15
400v 3ph 50Hz
6
1200x814x617
120
CMH5 & CUS5
13.5
7.5 or 15
400v 3ph 50Hz
6
1200x814x617
120
CMH6 & CUS6
18.8
7.5 or 15
400v 3ph 50Hz
10
1200x1215x617
123
CMH7.5 & CUS7.5
21.8
7.5 or 15
400v 3ph 50Hz
10
1200x1215x617
123
CMH10 & CUS5x2
26.6
7.5 or 15
400v 3ph 50Hz
10
1200x1215x617
164
CMH12 & CUS6x2
36.5
7.5 or 15 or 22.5
400v 3ph 50Hz
10
1200x1800x617
248
CMH15 & CUS7.5x2
42.5
7.5 or 15 or 22.5
400v 3ph 50Hz
16
1200x1800x617
248
Cooling Duty based on 27ºC Dry Bulb/ 19ºC Wet Bulb
and 35ºC ambient. Height of units varies up to a maximum
of 2160mm according to configuration. Nominal run amps and
recommended mains fuse relate to cooling only units.